    It would put phase directly on the metal casing of the appliance, if the circuit protection didn’t work.

    Please avoid the temptation to comment on something you know nothing about, this is actually a serious safety concern if someone followed this diagram.

    • fullsquare
      link
      fedilink
      arrow-up
      2
      ·
      11 months ago

      Even worse. Orientation of pins like this is used in 240V circuit which means it has two antiphase live wires. This means that after shorting them, if one trips but not the other (if these two have independent breakers - idk if code requires otherwise) 120V is sent to device ground, and this one can be cut off by GFCI if used, but i hear it’s uncommon

      If it was normal 120V circuit, breaker would cut off live and left neutral connected to device ground, which still can be some 20V depending on conditions

      • Ilovethebomb@sh.itjust.works
        link
        fedilink
        arrow-up
        2
        ·
        11 months ago

        Ooh, I hadn’t even thought about voltage being backfed through the neutral.

        Have you heard of something called a floating neutral? That could cause some issues.

        • fullsquare
          link
          fedilink
          arrow-up
          1
          ·
          11 months ago

          Yea, but at this point multiple things are seriously wrong